Brand Name : Kaixiang
Model Number : AC400-550kW
Certification : ISO9001
Place of Origin : China
MOQ : 1 set
Price : negotiable
Payment Terms : L/C, T/T, Western Union
Supply Ability : 30 Sets / Month
Delivery Time : Within 25 working days
Packaging Details : Packaged in wooden cases
Model : AC400-550kW
Rated power : 550 kW
Casing Color : as required
Rated voltage : AC400
Frequency : 50 HZ
Display Precision : 0.5 class
AC400-550kW Adjustable Load Bank In 3 phase 4 wire With Frequency 50 HZ
Introduction
(1) This system, which is of independent research and development of electricity load test equipment by our technology, combining dry load module with the automatic measurement and control module, can accurately detect all kinds of generator output power and load capacity, full load and overload test.
(2) The system consists of 1 sets of 500kW Resistive load bank. The System is made up of two parts of measurement and control and load, mainly including AC dry load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, PC software and so on.
Application
1. Ups system testing
2. Load optimization in prime power applications
3. Factory testing of turbines
4. factory testing of engine generator sets
5. To reducewet stacking problems
6. Periodic excercising of stand-by engine generator sets
Technical specification
System Parameters | |
Rated Voltage/ Frequency | AC 400V/50Hz, 3 phase 4 wire |
Max Load Power | Resistive Load: 550kW |
Load Step | 1,2,2,5,10,20,20,50,100,100,200kW, total 11 steps, can arbitrary combination between 1KW~510KW, min load precision is 1kw |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | AC380V/50Hz 3 phase 4 wire |
Wire Connection | Load Power Supply Input——Copper bar (star connection) Control power supply input——Aviation plug |
Insulation Class | F class |
Duty Cycle | Continuous |
Cooling | Forced air cooling,Horizontal inlet air,upwards outlet |
Transportation | Hoisting, with lifting lug on the top and castors at the bottom of casing |
Casing color | Grey (RAL7035) |
Dimension | About 1460 mm×1980mm×1800mm(L×W×H) |
Weight | About 900kg |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500m |
Atmospheric Pressure | 86~106kPa |
Load testing: Can load power that within the rated power, test and display stable state 3 phases voltage, current, active power, frequency, working time, etc of generator sets.
![]() |